fbpx

Understanding HVAC Diagnoses – Acidic Refrigerant

Year after year, lightning is consistently the most frequently claimed peril for HVAC systems in homeowner’s claims, and it is also the most often misdiagnosed cause of loss, according to the HVACi 2018 Annual Claims Report. One symptom that is regularly misinterpreted as lightning damage is acidic refrigerant in the system.

Contrary to popular belief among contractors, it is not possible for lightning to cause acid in the refrigerant circuit of an HVAC system. Instead, this symptom is caused by one of three conditions:  wear and tear, improper repairs, or a lack of system maintenance. Because this common misconception is often cited as an indicator of lightning damage, it is important for adjusters to understand why this is not the case.

Compressor oil tested positive for acid

The oil from a compressor was drained during destructive testing and tested positive for acid

What Causes Acidic Refrigerant

When the refrigerant circuit is subjected to moisture, excessive heat, contaminants, or other impurities, it leads to a chemical reaction that creates acid. This condition is brought about by age (ordinary wear and tear), a lack of maintenance, or an improper system repair. As a system ages, leaks can develop in the copper coils that contain the refrigerant, providing an point of entry for outside contaminants. Additionally, the compressor’s components can break down due to age, introducing impurities into the refrigerant. Once contaminants or moisture enter the refrigerant loop, the resulting chemical reaction will create acid. Acidic refrigerant can also occur when the system overheats due to a clogged coil or a failed condenser fan. Excessive heat caused by this lack of airflow can accelerate the creation of acid within the refrigerant. Finally, when a compressor burns out because of the presence of acidic refrigerant and is ultimately replaced (but the lineset is not properly flushed or a new filter drier is not installed) acid may be reintroduced into the new compressor, leading to another burnout.

Clogged coil leads to acidic refrigeration

A clogged coil can lead to elevated temperatures and accelerate the creation of acid

Organic vs. Inorganic Refrigerant Acids

Depending on the type of chemical reaction, the acid generated will be either organic or inorganic in nature. The type of refrigerant, oil composition, and the type of contaminant all influence this reaction. While both types of acids are destructive to compressors, the types of damage they cause are very different.

One factor in determining the composition of the acid produced is the combination of refrigerant and oil. Hydrochlorofluorocarbon (HCFC) systems, such as those that contain the refrigerant R-22, typically use mineral oil to lubricate the systems. When moisture or contaminants enter these systems, the refrigerant breaks down, because the natural lubricating oil is more stable than its accompanying refrigerant. This results in the creation of an inorganic acid. Such acids result in abnormally high temperatures in the motor windings and/or discharge area of the compressor. These high temperatures break down the windings and lead to the loss of electrical resistance of the compressor, or a compressor burnout.

Acidic refrigerant damages compressor motor windings

The above compressor motor windings were damaged by compressor burnout due to acidic refrigerant

Conversely, R-410a and other hydrofluorocarbon (HFC) systems use a polyolester (POE) lubricating oil, which has a very different chemical structure from HCFC/mineral oil systems. While the refrigerant itself is more stable, the oil composition is less stable and can break down easily in the presence of moisture, air, or high temperatures. When POE oils (as opposed to the refrigerant) break down, the resulting chemical reaction leads to the formation of organic acids rather than inorganic acids. Instead of leading to compressor burnout, organic acids typically create a sludge that can clog small valves or cause the oil to lose its ability to properly lubricate the compressor. When this occurs, the compressor will seize.

Positive acid test

This system tested positive for acidic refrigerant

Regardless of composition, HFC (R410a) and HCFC (R22) systems still run the risk of developing inorganic acids that can burn out the compressor. This can occur when contaminants and impurities (those not moisture, air, or excessive heat) enter the refrigerant system.  If contaminants (such as metals from the degeneration of the compressor) enter the system, an inorganic acid will form, leading to compressor burnout.

What does this mean for adjusters?

As an adjuster, you should always be on the lookout for any clues that a claim may need further investigation. It is critical that you understand what signs could be “red flags” when reviewing claims for complex equipment such as HVAC systems. A contractor’s attestation that points to acidic refrigerant as an indicator that a system has been damaged by lightning should always prompt a deeper discussion.

If you have a claim involving lightning damage to HVAC equipment, and you want to ensure an accurate settlement, you can submit your new claim here.

An Introduction to Evaporative Coolers

Evaporative coolers are a popular alternative to traditional refrigerant-based air conditioning units in regions with hot, dry climates. While they are not seen as frequently as traditional split systems and package units, adjusters should still make themselves familiar with this type of equipment, particularly if they handle claims in regions that are ideal for evaporative coolers.

What Is Evaporative Cooling?

Before we get into how evaporative coolers work, it is important to understand the principles behind evaporative cooling. The evaporative cooling process begins with the evaporation of water (or other liquid) into the surrounding air. When the liquid turns to a gas, it absorbs heat, thereby reducing the temperature of the surrounding air.

Evaporative Coolers - How the evaporative cooling process works

 

The concept of evaporative cooling has been around for thousands of years. The ancient Egyptians used this process to provide cooling by soaking fabric in water and hanging it across the door to the home. As the air passed through the fabric, it absorbed moisture and created a cool breeze in the space (How Stuff Works).

Get your copy of our Evaporative Cooler Claim Guide here

Evaporative Coolers - An inside view of an evaporative cooler

How Do Evaporative Coolers Work?

Evaporative coolers harness this process to provide cooling to a space. Residential properties typically utilize a direct evaporative cooler. In this type of system, a pump circulates water from a reservoir to saturate a cooling pad. A fan then pulls air from the outside through the wet pad, initiating the evaporation process. The cool, humid air is then distributed to the home.

There are three common types of direct residential evaporative coolers:

  • Portable Coolers – These are designed to cool a small living area. They do not require professional installation or ductwork. Some even come with wheels to make them easy to move from room to room.
  • Side Draft – These systems are installed so that the air blows from the side of the unit directly into the home. This type of evaporative cooler is installed either in the window or through the wall. These may require professional installation, but no ductwork. They will only be able to efficiently cool one room; however, they can provide cooling for a larger room or area than a portable cooler would.
  • Down Draft – These units are installed on the roof of a home and can provide cooling to the whole home through the use of a duct system. These are the most expensive to install and can be difficult to maintain.

Where Are Evaporative Coolers Effective?

To effectively use the evaporation process to create cooling, the air must be dry enough to absorb the moisture. Evaporative coolers are only consistently effective in areas where the relative humidity does not reach over 60%. Once the relative humidity reaches 60%, evaporative coolers can, at best, only lower the temperature by 10 degrees. Even in dry climates, when it does rain the humidity will rise. An evaporative cooler should not be used during these periods of high humidity.

Differences Between Evaporative Coolers and Traditional Air Conditioning Systems

Traditional air conditioning systems use a coil filled with refrigerant to transfer heat, provide cooling, and remove humidity from a conditioned space. This type of cooling system is a closed process, where the air from the room is cycled back through the cooling process. Allowing air to escape from the conditioned space will reduce the efficiency of the system.

How a downdraft evaporative cooler provides cooling to a home

Instead of using refrigerant, an evaporative cooler uses a pump to circulate water to the pads and a fan to pull air through the pads. This adds moisture to dry air and therefore requires the space to be ventilated so the moist air has a way out. Evaporative coolers do not always use ductwork to direct the airflow, but when they do, the ducts must be larger than traditional air conditioners to account for greater flow of air from the evaporative cooler.

Common Evaporative Cooler Issues

Evaporative coolers require frequent maintenance. The cooling pads need regular cleaning or replacement to avoid air quality issues and odors. This should be done as often as once per month when the evaporative cooler has been running constantly. Additionally, sediment and minerals can build up inside of the cooler. These need to be drained and cleaned at least once per season to keep the system working year after year. These tasks can become tedious, particularly when the system is mounted on the roof.

Growth from a pad of an evaporative cooler that was not maintained properly

The pads for this evaporative cooler had not been cleaned in so long that the build up has reached the pad’s guards

Evaporative Cooler Claim Considerations

The regions that are best for evaporative coolers tend to have a high propensity for hailstorms. Because evaporative coolers are often located on the roof, they are frequently included in a hail claim. Unlike condensing units, these systems do not have a coil that can be easily damaged by hail. Often, the unit shows no signs of damage from a hailstorm. However, large hailstones can dent the metal panels of the unit. While this does not generally affect the system’s operation, it still must be considered to sufficiently return the insured’s system to pre-loss condition. Luckily, these panels can typically be replaced as opposed to replacing the entire unit.

A hail damaged evaporative cooler

Hail broke through the top panel of this evaporative cooler, the top panels required replacement to return the insured to pre-loss condition

Additionally, compared to a standard HVAC system, an evaporative cooler has much fewer electrical components that could be damaged by an electrical event. Frequently, the evaporative cooler is activated by a simple variable-speed switch, therefore there are often no integrated circuit boards in the system. While the pump and electrical blower motor can still be damaged by a surge event, these occurrences are much less frequent than electrical damage to refrigerant-based systems.

While evaporative coolers are not as popular as the more traditional HVAC systems, adjusters (particularly those who handle claims in the western half of the country) should know what to look for when handling this type of unit on a claim. For more information on evaporative coolers, get your free adjuster guide here.

If you have a residential or commercial evaporative cooler claim that you need assistance with, submit your new assignment here. 

The Effect of Corrosion on Repairing Hail Damaged HVAC Coils

The following article on “Corrosion and Hail-Damaged HVAC Coil Repairs” originally appeared on Property Casualty 360

Wind and hail losses are the most frequently claimed homeowner’s insurance peril, causing approximately $1 billion in damages each year (III). HVAC systems, particularly condensing units and package units, have a high risk of hail damage. These systems, which sit outside either on the ground or the roof, contain a condenser coil constructed of copper tubing covered in a layer of malleable aluminum fins that facilitate heat transfer from the refrigerant to the surrounding air. When hail (or any other foreign object) strikes the coil, these fins can be bent and flattened, eventually reducing the ability for the coil to transfer heat efficiently.

Get Your Free Copy: 4 Things to Look for When Assessing Hail Damaged HVAC Systems

To return the unit to pre-loss condition, the coil should be restored to its original state before the hail occurred. The most common repair option for this kind of damage is to straighten the coil fins using a fin-combing tool (provided that the fins were not torn as a result of the damage). However, if the aluminum fins are in a corroded state, they may be too brittle to be properly straightened.

Corrosion can prevent the condenser coil fin straightening as an option following hail damage

Hail damaged condenser coils can often be straightened using a fin combing tool

Corrosion of the coil

Although aluminum is ideal for outdoor applications, like any metal exposed to the elements, a condenser coil is susceptible to long-term corrosion. As corrosion begins to deteriorate the composition of the condenser coil, it weakens its integrity, making the fins difficult to straighten through traditional methods.  Certain conditions accelerate the corrosion of an outdoor coil, and may include the following:

Proximity to Saltwater

When saltwater comes in contact with the metals of a condenser coil, corrosion will be accelerated and pitting will likely occur. This air-borne saltwater can be carried by spray, mist, rain or fog, and can impact systems located more than 5 miles from the coast. Once the coil has begun to corrode (which can happen very quickly in a harsh coastal environment) the coil’s ability to be easily combed will be impeded.

Corrosion can be caused by a harsh coastal environment

The harsh coastal environment caused the severe corrosion of this condenser coil

Industrial and Urban Areas

During the combustion of coal and fuel oils, sulfur and nitrogen oxides are released. These atmospheric emissions are frequently found in both industrial and urban environments. The particles of these oxides are highly corrosive when they combine with oxygen, water, or high humidity conditions, which can lead to corrosion of the metals exposed to these harsh environments.  The common placement of HVAC equipment near these emission sites further exacerbates the issue.

Read More: Hail Damage to HVAC Condenser Coils 

Bi-Metal Coil Construction

Galvanic (or bi-metal) corrosion occurs when dissimilar metals come in contact with one another and an electrolyte (such as water).  When this condition exists (which it frequently does, due to common coil construction and their outdoor placement), corrosion will be accelerated in the “less noble” of the two metals.  Because the aluminum fins in the condenser coil are less noble than the copper tubing contained within, and the coil is frequently wet, electrons freely flow away from the aluminum to the copper, causing the aluminum to degrade over time.

Corrosion can cause the fins of a condenser coil to be too brittle to starighten

A hail damaged condenser coil that required replacement because the corroded fins were too brittle to straighten

Get Your Free Copy: HVAC Hail Damage Repair Hierarchy 

Sprinkler Systems

Water that has a low pH value, low alkalinity, or contains total dissolved solids such as inorganic salts, can accelerate condenser coil corrosion.  When untreated water (most often, well water) is used in lawn sprinkler systems, its effect on exposed metal surfaces could be problematic.  Condenser coils that are in the path of sprinkler systems using untreated water are subject to the potential of accelerated corrosion.

Although this system sustained minor hail damage, it was in the path of a sprinkler system, which corroded the coils and rendered them too brittle to be straightened

Although this system sustained minor hail damage, it was in the path of a sprinkler system, which corroded the coils and rendered them too brittle to be straightened

Cleaning Agents

Many condenser coil cleaning agents contain sodium hydroxide and are highly caustic. If these agents are not thoroughly rinsed (with neutral pH water) after cleaning the coil, they can deteriorate the aluminum fins quickly. Certain household cleaners, such as bleach, vinegar, and hydrochloric acid are corrosive to aluminum and should not be used.  Moreover, some cleaning agents which may be suitable for aluminum may not be advised for copper, thus, both metals must be taken into consideration when choosing the appropriate agent.

Corrosion Prevention

Protective coatings may prevent or slow coil corrosion in high-risk areas.  For this reason, condenser coil coatings have become a popular choice for HVAC equipment manufacturers and maintenance organizations. Coatings can be applied by the manufacturer during production or by a service technician after the system has been installed.

The coil coating that is applied in the factory is dipped and baked on, so that the application is even and covers the entire coil. If the coating is applied in the field, the coating is likely to be less evenly applied and therefore, less effective.  If the field-based coating is too thick, the coil’s fins may be difficult to straighten after hail damage. And because the entire coil may not be coated, corrosion can still occur. Finally, if the coil is not properly cleaned before the coating is applied (or if it is coated after corrosion has already begun), the full benefit of corrosion prevention will not be realized.

Conclusion

While aluminum is ideal for HVAC condenser coil construction, due to its natural corrosion prevention characteristics, no metal is completely immune from corrosion.  Insurance professionals would be wise to understand the factors that contribute to coil corrosion, and the steps that can be taken to mitigate its impact on HVAC claim settlement options.

The Impact of HVAC Theft on Property Claims

One in every 235 homeowners files a theft claim each year. These damages average nearly $4,000 per paid claim, according to the Insurance Information Institute. A major contributing factor to these staggering theft claim statistics is HVAC theft.

HVAC theft of coils from multiple units

Theft of coils from multiple HVAC units

Why is HVAC theft such a common occurrence?

HVAC systems include valuable metals that criminals can easily sell. The placement of the units in accessible areas makes HVAC systems vulnerable to theft.  The condensing unit is located outdoors and is often placed out of plain sight, especially on commercial buildings, making it very easy for thieves to access without drawing attention to themselves. The desired components can be stolen quickly and easily, if the property owner has not taken preventative steps.

HVAC Theft copper lineset

Copper lineset cut and removed

The outdoor portion of the HVAC system contains valuable copper, which is a hot ticket item for thieves. Stolen copper can be sold to scrap yards for up to 90% of its current value. Copper theft has more than tripled in the past five years, and the amount of copper stolen annually exceeds $1 billion (20 Extraordinary Copper Theft Statistics). While the price of copper has declined slightly since its peak in 2011, the value has steadily increased over the past year to $2.91 per pound at the time of this writing (Investment Mine).

HVAC Theft

Whole condensing unit stolen from pad

Additionally, the rising number of copper thefts over the past 5 years led some states to enact stricter regulations on scrap yards, requiring locations to enforce more stringent requirements when accepting salvaged copper.  This has resulted in some thieves removing full units, as opposed to simply stealing copper coils and linesets (Copper Theft: The Next Gold Rush).

What considerations are required for a repair or replacement option following theft?

The main consideration following theft of HVAC components for determining scope of repairs is what components were stolen. However, the theft of a few components can create a domino effect, leading to a major repair or a full system replacement. A few additional factors need to be taken into consideration before determining the scope of repairs required to return the insured to pre-loss condition.

Amount of time passed since the theft

When a thief is stealing copper or the outdoor condensing unit, they will have to cut the lineset that connects the outdoor compressor to the indoor evaporator coil. If the lineset is left open, moisture and contaminants can enter the refrigerant loop and lead to a major repair or replacement requirement. The length of time the lineset can remain open depends mainly on the type of refrigerant used in the system. HCFC refrigerants, such as R-22, can typically remain open for a longer period than HCF refrigerants, like R410a. This is because HFC systems use polyolester (POE) oil in the compressor that is more impacted by moisture in the atmosphere than the mineral oil traditionally used in HCFC refrigerant compressors. Some newer R-22 compressors also use POE oils, so the age of the system needs to be taken into consideration, in addition to the type of refrigerant.

HVAC Theft: Copper Lineset Cut

Copper lineset cut from condensing unit compressor

Equipment Availability

Some theft damages may require a more extensive repair or even a full system replacement due to the availability of repair parts. This is especially prevalent in older systems. For example, if the coils are stolen and there are no longer compatible coils available from the manufacturer, the outdoor condensing unit may need to be replaced to return the insured to pre-loss condition. This could increase the recommended settlement amount by thousands of dollars.

Federal Regulations

Currently, there are federal regulations surrounding HVAC systems that are enforced by the Department of Energy (DOE) and the Environmental Protection Agency (EPA). The DOE regulates the minimum efficiency standard of newly installed equipment. The efficiency of an HVAC unit is rated by the seasonal efficiency ratio (SEER). If a split system is damaged by theft and as a result, the outdoor condensing unit needs to be replaced, the new unit must meet the minimum efficiency requirements (currently 14 SEER in the south and southeast, 13 SEER in the north). The SEER rating of the remaining indoor equipment must be taken into consideration because of the potential for SEER mismatch between new and old equipment.

HVAC Theft: DOE Efficiency Changes

Current EPA regulations are phasing out the production of net-new R-22 refrigerant through 2020. Though R-22 is still being produced and parts are still being manufactured, it is becoming increasingly difficult to find dry shipped condensing units that meet the current DOE SEER requirements. Moreover, R-22 systems cannot be retrofitted to use R410a refrigerant. This means that if the outdoor condensing unit is stolen or needs to be replaced, the indoor coil may also require replacement.

HVAC Theft: R-22 Phaseout Chart

How can we reduce the risk of HVAC theft?

There are many steps that property owners can take to reduce the risk of HVAC theft and, subsequently, thousands of dollars in insurance losses, including:

  • Improve or add lighting surrounding the unit to increase visibility. Because the HVAC unit is often tucked away out of sight on the property, outdoor lighting may not illuminate it, making it easy for a potential thief to access. An even better option is to install motion-censored lights, which will activate when someone walks in the path of the motion detector.
  • Install metal cages around the HVAC equipment. Manufacturers produce HVAC system specific security cages, which allow the unit to be locked away from theft, while maintaining the airflow required for the system to operate properly.
  • Incorporate an HVAC alarm system. These alarm systems typically connect to a standard security system. If power is manually shut off to the HVAC system, or the refrigerant pressure levels suddenly drop, it triggers the security system.
  • Add a video surveillance system and signs that notify potential culprits that the site is being recorded, which will deter many thieves. If a theft does occur, video footage of the crime can be accessed, which can potentially assist in finding the culprit.

HVAC theft prevention

Condensing unit enclosed in security cage to prevent theft

What does this mean for insurance carriers?

As long as HVAC theft remains a prevalent concern, it is critical that insurance carriers take all steps necessary to reduce indemnity leakage. This can be achieved by ensuring that claims are settled for a proper repair scope, as opposed to simply replacing every system subjected to a theft. Additionally, agents and risk managers can help policyholders to properly reduce the risk of HVAC theft and reduce the exposure of insurance carriers for theft claims.

Identifying Lightning Damage to HVAC Systems

Lightning strikes the earth about 100 times every second and can heat the surrounding air to up to 50,000 degrees Fahrenheit (The Weather Channel). As such a destructive force, it’s no wonder lightning damage caused $790 million in homeowners insurance losses in 2015 and an average of almost $8,000 per paid claim (Insurance Information Institute). Moreover, these amounts are expected to rise as the average number and value of electronics within a home increases.

The rising cost of lightning damage claims illustrates the importance to insurance carriers of properly identifying the peril prior to making a settlement decision. According to a study conducted by Vaisala of 14,000 lightning claims from a top insurance carrier, 30% had no recorded lightning strikes in the vicinity. If each of those claims were settled for the average settlement amount of $8,000, that would have resulted in over $33 million of indemnity leakage.

To make matters worse for claims involving HVAC equipment, many symptoms of age-related wear & tear are often misdiagnosed as lightning damage. We’ve put together an overview that illustrates the symptoms of lightning, surge, and wear & tear damages, to help adjusters settle lightning claims with a greater degree of accuracy.

Lightning Damage

The outdoor placement of the condensing unit or packaged unit lends itself to direct lightning damage. This type of damage is almost always limited to the outdoor equipment. With confirmed lightning damage, there will always be visual evidence of arcing and charring of the equipment casing and/or housing. Additionally, multiple outdoor electrical components will be damaged, such as the contactor, capacitor, compressor, and fan motor.

Lightning Damage to the Disconnect Box

Visual evidence of a direct lightning strike to the disconnect box

While lightning damage is the most frequently claimed cause of loss to HVAC equipment, lightning is very rarely the actual peril to the system. Most often, HVAC systems reported as a lightning damage are in fact damaged by wear & tear, surge or, perhaps worse, not damaged at all.

Surge Damage

A voltage surge occurs when there is a spike in the home’s or business’ electrical current. While this could be caused by a nearby lightning strike, it could also be the result of the utility company switching grids, or even internally when larger appliances turn on and off (State Farm’s Simple Insights).

Lightning Damage

Surge damage to the capacitor, contactor, and wiring

Surge damage in an HVAC system is typically much less severe and more common than direct lightning damage. A surge could cause damage to multiple components and often includes the contactor and capacitor. Additionally, large portions of wires will often show visual signs of overheating in the form of melting and/or arc marks in surge events.

Wear & Tear Damages

Many symptoms that are actually caused by age-related wear & tear are often misdiagnosed as lightning damage to an HVAC system. In fact, in 2016, 48% of claims reported as lightning damage were found to have failed due to wear & tear following an objective damage assessment.

Claimed Lightning Damage - Actually Wear & Tear

Wiring charred within 2″ of the connection to the capacitor indicating there was a loose connection

One major indication that the damage was simply caused by age-related wear & tear is when a single component fails, such as the compressor only or capacitor only. Another sign of wear & tear is charred wiring within 2” of the component connection, as this is typically a sign of loose wiring connections. The final misdiagnosed lightning symptom is acid in the refrigerant. Acid builds over time when moisture or contaminants enter the refrigerant, and does not occur instantaneously following a lightning or surge event.

The frequency of lightning claims (and often their misdiagnosed symptoms) underscores the importance of engaging an objective expert prior to making a coverage decision. By ensuring that lightning claims are settled accurately, insurance carriers can reduce their risk of indemnity leakage.

4 Options to Consider When Adjusting Hail Claims

The following article on “4 Options to Consider When Adjusting Hail Claims” was originally published on Property Casualty 360.

The first few months of 2016 ushered in severe weather storms of historical proportions.

According to the Property Claims Service unit of Jersey City, N.J.-based Verisk Solutions, first-quarter losses added up to an estimated $3.8 billion, 27% higher than the 10-year first quarter average.

Hail Claims
The Insurance Information Institute says hail causes about $1 billion in damage annually, with the highest number of claims reported in April, May and June. Hail guards like this one can help reduce some of the damage to HVAC systems.

This is in large part because of hailstorms that ripped across much of the country.

Download our adjuster guide to hail claims

Two devastating storms, separated by a week, hammered the Dallas-Fort Worth area in March. In April, San Antonio was hit with the costliest hail event in Texas history, according to the Independent Insurance Agents of San Antonio, which included hail up to 4½ inches in diameter, the National Weather Service said. Less than a month later, major hailstorms stretched from Kansas and Oklahoma, all the way to the Atlantic coast.

As a result of these catastrophic losses (and several other minor hail storms), many adjusters have found themselves in uncharted territory, tasked with handling heating, ventilation and air-conditioning (HVAC) losses they’re not accustomed to settling.

When encountering hail claims, it’s important to understand what HVAC parts are truly susceptible to damage, and what repair methods are readily available to return the insured to pre-loss condition.

Exposed and delicate

Aside from roofing and siding, HVAC systems account for the most commonly claimed residential property loss because of hail damage. The outdoor condensing unit, and more specifically, the condenser coil, is the most susceptible component of an HVAC system to sustain damage from hail. The condenser coil contains tightly spaced aluminum “fins” that surround the perimeter of the condensing unit. And because of they are made of thin, malleable aluminum, they can easily be damaged by any foreign object, including hailstones.

Because of their susceptibility to hail damage, some residential and commercial condenser coils are protected by hail guards (rigid metal casing with vents to allow airflow). However, most HVAC systems are not equipped with hail guards, resulting in dented, bent, and even torn fins, in rough proportion to the size of the hailstones during these events.

When it comes to returning HVAC systems to their pre-loss condition (regardless of whether they’re rooftop-based units or traditional split systems), the overwhelming majority of systems with confirmed hail damage can be restored with minor to moderate repairs.

In fact (much to the dismay of some local contractors), a “hierarchy” of repair options exists for hail-damaged HVAC systems, and should be considered when faced with this type of claim:

Hail claims: HVAC repair hierarchy
This pyramid gives adjusters with a hierarchy for evaluating damage to HVAC systems.
Hail Claims: Before and after combing
At left, minor hail damage that dented the fins of the condensing coil of a residential split system condensing unit. At right, fins after combing.

Option 1: Comb the fins

The first (and statistically most likely) repair option in the hail repair hierarchy is to straighten or “comb” damaged condenser coil fins with a specialty tool designed for this specific purpose.

In fact, nearly 50% of all residential HVAC systems with hail-related damages assessed in 2015 could be restored to pre-loss condition using this repair method, according to the HVACi 2016 Annual Claims Report.

If an HVAC professional invests adequate time and care into the work, combing the fins of a condenser coil is often a simple and inexpensive way to rectify minor hail damage.

Hail Claims: Moderate Hail Damage
Close-up view of moderate hail damage to a commercial unit.

Option 2: Replace the coil

If the hail damage proves too extensive to comb the condenser coil fins, the second step in the repair hierarchy is to repair the HVAC system by replacing the condenser coil itself.

Thirty percent of the hail claims assessed in 2015 resulted in this repair recommendation following an onsite investigation of the system damage. Many condenser coils are stocked at local HVAC distribution centers or manufacturer warehouses, and in other cases, can be produced by the manufacturer “on demand” if needed.

Hail Claims: Major Damage
Significant damage to a commercial rooftop package unit.

Option 3: Replace the condensing unit

If the condenser coil is no longer available, or the lead-time for the coil production is too long, adjusters may opt to replace the outdoor condensing unit or packaged unit.

As the third step in the hail repair hierarchy, this repair option is required less often than a combing (step 1) or replacing the condenser coils (step 2). That said, condensing unit replacements were required roughly 17% of the time for residential hail claims last year, and remain a viable repair action of last resort.

Option 4: Replace the system

If replacing the condenser coil isn’t a viable repair option, and the condensing unit replacement results in a significant mismatch with the remaining internal equipment, adjusters may be compelled to authorize a full system replacement. However, it’s important to note that this scenario is highly unlikely and very infrequent. In fact, only 5% of residential hail claims in 2015 required a full-system replacement (meaning 95% of hail-damaged HVAC systems can be repaired and returned to pre-loss condition).

HVAC systems damaged by hail very rarely require replacement. When handling hail losses, adjusters who receive a local contractor’s estimate stating that full system replacement is required should view to do some additional digging. Data suggests that other options are not only available, but are likely to be the prudent path to system restoration.

The Dangers of Freezing Water & Boilers

The following article on “The Dangers of Freezing Water & Boilers” originally appeared in the Technical Notebook Column of Claims Magazine and was also published on Property Casualty 360

Stuck low water cutoff for boilers can be dangerous
Figure 1 and an inside view of a stuck, low-water cutoff in a boiler

As we enter the heart of winter and turn our attention toward cold weather conditions where freezing water can wreak havoc on commercial and residential property, the threat of catastrophic failure to boilers looms large (as seen in Figure 1).

Although failsafes against significant boiler failures do exist and continue to improve, they remain far from perfect.

One particularly susceptible failsafe is a boiler’s low water cutoff (LWCO). An LWCO is designed to alert the boiler that it does not contain sufficient water to “fire,” and prevents the boiler’s burners from igniting until a safe water level has been restored.

Installation of low water cutoffs 

Because these types of failures can lead to injury or death, most state and municipality codes require the installation of low water cutoffs for both residential and commercial boiler applications.

LWCOs are found in one of two designs: Electronic-probe (a more recent technological introduction) and mechanical-float (a traditional, lower-tech version, seen in Figure 2). For this article, we’ll focus our attention on the latter.

What is a mechanical-float LWCO? 

Mechanical-float low water cutoffs are the most widely used water-level safety device in residential and commercial heating boiler applications. These LWCOs are simple in design and function much like fill arms found in residential toilet tanks. As the water level drops in a boiler reservoir, the buoyant arm “floats” down until it reaches a point at which the boiler is unsafe to operate, and the switch turns the heating system off as illustrated in Figure 3.

Common issues with LWCO valves 

Despite their simplistic design, mechanical-float LWCOs are prone to several issues, which can have catastrophic impact if not addressed. These issues include:

  1. Stuck valves: Mechanical-float LWCO valves are in constant contact with supply water, and are exposed to minerals, dirt, rust and other total dissolved solids (TDSs). This prolonged exposure to TDSs can interfere with the designed function of the float, preventing it from moving freely up and down in line with the actual water level.
  2. Clogged LWCOs: Sometimes, TDSs and other impurities can prevent the free-flow of water through the LWCO, and can “trick” the LWCO into reporting that an adequate supply of water is present in the boiler, when in fact the minimum safe water level has been breached.

Consequences of LWCO failure 

If the float is prevented from moving freely and from sending the appropriate signal to the boiler controls (and the burner) to shut down the boiler when the minimum safe water supply level has been breached, the boiler may continue to run without water (or may be allowed to start without water present).

If a boiler operates without the necessary water supply, the heat generated in the boiler’s combustion chamber does not transfer to the water supply, and causes the burner, heat exchanger, and/or boiler tube(s) to overheat. With prolonged or repeated exposure to this condition, the walls of the burner, boiler or heat exchanger may weaken and ultimately crack, as seen in Figure 4.

Freezing conditions, when coupled with LWCO failure, can lead to catastrophic system failure. Should the feedwater pipes for the boiler become frozen (a common occurrence during cold winter months), the system will be starved of water. If the LWCO simultaneously malfunctions, the boiler will start and run without an adequate supply of water.

The cost of LWCO failure 

When the heat exchanger or boiler tubes crack or fail, the cost associated with the required labor and parts to repair the boiler (provided the parts are still available since boilers can remain in service for dozens of years) often outweigh the cost of the replacement. The failure of a relatively inexpensive component (usually between $200 and $600, plus installation) can ultimately lead to a residential settlement in excess of $10,000.

Mechanical-float failure prevention 
Mechanical-float LWCO valves should be regularly “flushed” to remove TDSs which can prevent the float from moving freely as the water level within the boiler changes. Most manufacturers recommend flushing the boiler at least once per season (some field technical experts say as often as weekly) by opening the “blow down valve,” which sits beneath the LWCO line and allows harmful deposits to escape. Boiler feedwater should be chemically treated to prevent scaling and to maintain proper pH levels for optimal boiler efficiency and performance.

The prevalence of boilers in residential and commercial heating applications makes the threat of LWCO failure real.